Cf300x Range Extinguishing Control Panel

Summary/ Overview


The CF300X control panel is designed in accordance with European standards EN54-2 Fire detection and fire alarm systems. Control and indicating equipment and EN54-4 Fire detection and fire alarm systems. Power supply equipment.

Product Description/ Features/ Specifications


The CF300X control panel is designed in accordance with European standards EN54-2 Fire detection and fire alarm systems. Control and indicating equipment and EN54-4 Fire detection and fire alarm systems. Power supply equipment.

Approved to EN12094-1 fixed fire fighting systems - components for gas extinguishing systems - Part 1.

The CF300X is compatible with all of Eaton's range of conventional detectors, manual callpoints and sounders.

The control equipment is a combined fire alarm control panel and extinguishing system and has three detection zones, any or all of which are capable of contributing to the release decision.

Features

  • Test condition
  • Delay of the actioning of fire alarm devices (sounders)
  • Fire alarm devices to enable an audible warning to be sounded throughout premises upon the detection of a fire condition or the operation of a manual callpoint
  • Voltage free relay contacts for fire
  • Delay of extinguishing signal of up to 60 seconds
  • Signal representing the flow of extinguishing agent to indicate
  • the released condition
  • Monitoring of the status of components by way of a low
  • pressure switch input
  • Emergency hold device to enable the extinguishing delay time to be extended
  • Control of flooding time to deactivate the releasing output after a set period of time
  • Manual only mode to disable the release of extinguishing via automatic detection devices
  • Triggering of equipment outside the system by way of first and second stage contacts, extract fan output
  • Activation of alarm devices with different signals to indicate pre-discharge and released warnings using different sounds

Code

CF300X

Construction

1.2mm mild sheet steel

IP Rating

IP30

Finish

Epoxy powder coated

Colour – lid & box

BS 00 A 05 grey – fine texture

Colour – controls plate & label

RAL 7047 light grey – satin

Weight

6kg

Mains Supply

230V AC +10%/-15% (100 Watts maximum)

Mains Supply fuse

1.6 Amp (F1.6A L250V)

Power supply rating

3 Amps total including battery charge 28V +/- 2V

Maximum ripple current

200 millivolts

Battery type (Yuasa NP)

Two 12 Volt 7Ah sealed lead acid in series

Battery charge voltage

27.6VDC nominal (temperature compensated)

Battery charge current

0.7A maximum

Battery fuse

20mm, 3.15A glass

Maximum current draw from batteries

3 Amps

Quiescent current of panel in mains fail

0.095A

R0V output

Fused at 500mA with electronic fuse

Sounder outputs

24V Fused at 500mA with electronic fuse

Fault relay contact rating

30VDC 1A Amp maximum

Fire relay contact rating

30VDC 1A Amp maximum

Local fire relay contact rating

30VDC 1A Amp maximum

First stage contact rating

30VDC 1A Amp maximum

Second stage contact rating

30VDC 1A Amp maximum

Extract contact rating

30VDC 1A Amp maximum

Zone quiescent current

2mA maximum

Terminal capacity

0.5mm² to 2.5mm² solid or stranded wire

Number of detectors per zone

Dependent on type (maximum 32)

Number of sounders per circuit

Dependent on type (max. 0.5A per sounder circuit)

Detection circuit end of line

6K8 5% ½ Watt resistor

Monitored input end of line

6K8 5% ½ Watt resistor

Sounder circuit end of line

10K 5% ¼ Watt resistor

Extinguishant output EOL

1N4004 Diode

No. of detection circuits

3

No. of sounder circuits

2 x 1st Stage, 1 x 2nd Stage

Extinguishant release output

Fused at 1 Amp

Extinguishant release delay

Adjustable 0 to 60 seconds (in 5 second steps)

Extinguishant release duration

Adjustable 60 to 300 seconds (in 5 second steps)

SIL, AL, FLT, RST inputs

Switched -ve, max resistance 100 Ohms

Zone normal threshold

8K ohms to 1K ohm

Detector alarm threshold

999 ohms to 400 ohms

Call point alarm threshold

399 ohms to 100 ohms

Short circuit threshold

99 ohms to 0 ohms

Head removal condition

15.5 to 17.5 volts

Cabling

FP200 or equivalent

Monitored inputs normal threshold

8K ohms to 1K ohm

Monitored inputs alarm threshold

999 ohms to 100 ohms

Monitored inputs Short circuit threshold

99 ohms to 0 ohms

Status unit/Ancillary board connection

Two wire RS485 connection

Status unit power output

Fused at 500mA with electronic fuse