The CF300X control panel is designed in accordance with European standards EN54-2 Fire detection and fire alarm systems. Control and indicating equipment and EN54-4 Fire detection and fire alarm systems. Power supply equipment.
Approved to EN12094-1 fixed fire fighting systems - components for gas extinguishing systems - Part 1.
The CF300X is compatible with all of Eaton's range of conventional detectors, manual callpoints and sounders.
The control equipment is a combined fire alarm control panel and extinguishing system and has three detection zones, any or all of which are capable of contributing to the release decision.
Code |
CF300X |
---|---|
Construction |
1.2mm mild sheet steel |
IP Rating |
IP30 |
Finish |
Epoxy powder coated |
Colour – lid & box |
BS 00 A 05 grey – fine texture |
Colour – controls plate & label |
RAL 7047 light grey – satin |
Weight |
6kg |
Mains Supply |
230V AC +10%/-15% (100 Watts maximum) |
Mains Supply fuse |
1.6 Amp (F1.6A L250V) |
Power supply rating |
3 Amps total including battery charge 28V +/- 2V |
Maximum ripple current |
200 millivolts |
Battery type (Yuasa NP) |
Two 12 Volt 7Ah sealed lead acid in series |
Battery charge voltage |
27.6VDC nominal (temperature compensated) |
Battery charge current |
0.7A maximum |
Battery fuse |
20mm, 3.15A glass |
Maximum current draw from batteries |
3 Amps |
Quiescent current of panel in mains fail |
0.095A |
R0V output |
Fused at 500mA with electronic fuse |
Sounder outputs |
24V Fused at 500mA with electronic fuse |
Fault relay contact rating |
30VDC 1A Amp maximum |
Fire relay contact rating |
30VDC 1A Amp maximum |
Local fire relay contact rating |
30VDC 1A Amp maximum |
First stage contact rating |
30VDC 1A Amp maximum |
Second stage contact rating |
30VDC 1A Amp maximum |
Extract contact rating |
30VDC 1A Amp maximum |
Zone quiescent current |
2mA maximum |
Terminal capacity |
0.5mm² to 2.5mm² solid or stranded wire |
Number of detectors per zone |
Dependent on type (maximum 32) |
Number of sounders per circuit |
Dependent on type (max. 0.5A per sounder circuit) |
Detection circuit end of line |
6K8 5% ½ Watt resistor |
Monitored input end of line |
6K8 5% ½ Watt resistor |
Sounder circuit end of line |
10K 5% ¼ Watt resistor |
Extinguishant output EOL |
1N4004 Diode |
No. of detection circuits |
3 |
No. of sounder circuits |
2 x 1st Stage, 1 x 2nd Stage |
Extinguishant release output |
Fused at 1 Amp |
Extinguishant release delay |
Adjustable 0 to 60 seconds (in 5 second steps) |
Extinguishant release duration |
Adjustable 60 to 300 seconds (in 5 second steps) |
SIL, AL, FLT, RST inputs |
Switched -ve, max resistance 100 Ohms |
Zone normal threshold |
8K ohms to 1K ohm |
Detector alarm threshold |
999 ohms to 400 ohms |
Call point alarm threshold |
399 ohms to 100 ohms |
Short circuit threshold |
99 ohms to 0 ohms |
Head removal condition |
15.5 to 17.5 volts |
Cabling |
FP200 or equivalent |
Monitored inputs normal threshold |
8K ohms to 1K ohm |
Monitored inputs alarm threshold |
999 ohms to 100 ohms |
Monitored inputs Short circuit threshold |
99 ohms to 0 ohms |
Status unit/Ancillary board connection |
Two wire RS485 connection |
Status unit power output |
Fused at 500mA with electronic fuse |