Summary/ Overview


An extensive range of micro interfaces are available to support the Cooper range of control panels, providing solutions for most design requirements.

Product Description/ Features/ Specifications


An extensive range of micro interfaces are available to support the Cooper range of control panels, providing solutions for most design requirements.

The MCIM is a single input, soft addressed micro interface, incorporating integral short circuit isolators. It is extremely compact and therefore ideal for incorporation into other equipment.

The MCIM is fully compatible with the current range of Cooper intelligent addressable fire control panels. It is suitable for monitoring a set of normally open, volt free contacts such as sprinkler system flow switches, auxiliary panel fire/fault signals as well as non fire input signals such as flow valve open contacts, generator start up, fire door closed etc.

Features

  • Soft addressed
  • Integral short circuit isolator
  • Single address
  • Suitable for monitoring:
  • - Flow switches
  • - Non fire inputs
  • - Auxillary panels
  • Up to 200 units per loop

Benefits

  • Quick and simple to install
  • No hard addressing required (Plug and play)
  • Compact size
  • Programable by Cooper site installer software as technical input/non fire input

Code

MCIM

Description

Micro Single Channel Intput Unit

Standards

En54 Pt17& Pt 18

Specification

Operating Voltage

18V dc to 30V dc

Quiescent Current

310µA

Inputs

Trigger Resistance

5K6Ω

End of Line Resistor

22KΩ

Short Circuit Fault

Threshold Resistance

1KΩ

Open circuit Fault

Threshold Resistance

33KΩ

Environmental

Operating temperature

-10oC to +60oC

Humidity (Non Condensing)

0 to 95% RH

Physical

Construction

PC/ABS

Dimensions (HxWxD)

65mm x 35mm x 18.5mm

Weight

0.078kg

Ingress Protection

IP40

Compatibility

Suitable for use with

Cooper Intelligent Addressable Fire Systems

 