Summary/ Overview


These addressable mimic relay boards, CIOP4 and CIOP8, are 4 and 8 way soft addressing output modules, incorporating integral short circuit isolators.

Product Description/ Features/ Specifications


These addressable mimic relay boards, CIOP4 and CIOP8, are 4 and 8 way soft addressing output modules, incorporating integral short circuit isolators.

Both the CIOP4 and the CIOP8 mimic relay boards are fully compatible with the current range of Cooper intelligent addressable control panels. The units are suitable for switching low voltage (24V dc at 1A maximum), via a set of non latching relay contacts.

The flexibility of these modules is further enhanced by the fact that each output can be programmed for a range of triggers such as disablement, fault, fire, test panel, test zone prealarm, fire routing equipment, fire protecting equipment and reset with up to 16 different trigger sources per output.

The trigger source can be global, by panel, by loop, by zone or by address. The logic is available in both OR & AND functions.

These units have an additional 4 inputs which can initiate a reset, silence, evacuate and test function.

They can be programmed using the CF3000 programmable site installer software and downloaded using the RS232 port.

Features

  • Loop powered
  • Units can be soft or hard addressed
  • Integral short circuit isolator
  • Single address
  • 4 input, 4 output version
  • 4 input, 8 output version
  • PCB version incorporates 4 inputs:
  • - Reset
  • - Silence
  • - Evacuate
  • - Test
  • 16 settings per output
  • Trigger types: fire, fault, disablement, test, prealarm, FRE, FPE, reset
  • Trigger source: global, by panel, by loop, by zone, by address
  • Logic functions (OR & AND)

Benefits

  • Quick and simple to install
  • Pluggable terminals for ease of wiring
  • Programmable via site installer software
  • Cost effective installation solution

Code

CIOP4, CIOP8

Description

4 Way Mimic Relay Board (CIOP4)

8 Way mimic Relay Board (CIOP8)

Specification

Operating Voltage

24V dc to 30V dc

Operating Loop Voltage

18V dc to 30V dc

Current

1A (max)

Quiescent Current

6mA (nom)

Environmental

Humidity (Non Condensing)

0 to 95% RH

Physical

Construction

Boxed ABS

Dimensions (HxWxD)

Boxed - 180mm x 244mm x 63mm

Board – 113mm x 163mm

Weight

Boxed - 1.2kg/ Board - 180kg

Ingress Protection

Boxed - IP65

Compatibility

Suitable for use with

Cooper Intelligent Addressable Fire Systems

Proceed to Checkout Now →