An extensive range of interfaces are available to support the Cooper range of control panels, providing solutions for most design requirements.
The shop monitor unit (MSU840) is designed to enable small units with conventional fire detection to be fully integrated with a main intelligent addressable fire system.
This unit is ideal for applications such as connecting individual shop units into a main shopping centre system.
An external power supply is required to drive the 2 conventional sounder circuits. This power supply must be regulated for fire and current limited.
Code |
MSU840 |
---|---|
Description |
Shop Monitor Unit |
Standards |
EN54 Pt17 & Pt18 |
Specification |
|
Operating Voltage |
15V dc to 30V dc |
Quiescent Current |
3.4mA (max) |
Quiescent Load Current |
2.8mA (max) |
Alarm Current |
8mA (max) |
Zone Circuits |
|
Number Input Circuits |
2 |
Zone Circuit 1 |
Callpoints only |
Zone Circuit 2 |
Detectors and Callpoints |
Number of Call points |
Unlimited |
Call point Resistance |
470Ω to 680Ω |
Zone Circuit 1 EOL |
6K8 |
Zone Circuit 2 EOL |
Active EOL |
Number of Detectors |
20 (max) |
Short Circuit Fault Threshold |
150Ω |
Open Circuit Fault Threshold |
N/A active EOL |
Sounder Circuits |
|
Number of Sounder Circuits |
2 |
Load per Output |
300mA (max) |
Sounder Circuit 1 and 2 EOL |
12K |
Relay |
|
Fire Relay Single Pole C/O |
1A at 30V dc |
Environmental |
|
Operating Temperature |
-10°C to +60°C |
Humidity (non condensing) |
0 to 95% RH |
Physical |
|
Construction |
PC/ABS |
Dimensions (HxWxD) |
129mm x 180mm x 60mm |
Weight |
1kg |
Ingress Protection |
IP40 |
Compatibility |
|
Suitable for use with |
Cooper Intelligent Addressable Fire Systems |