The ULMCIM and ULMCIM-C are designed for use with water flow switches and other applications requiring the monitoring of dry contact alarm devices.
The ULMCIM and ULMCIM-C are single channel input units and are extremely compact and therefore ideal for incorporation into other equipment.
The ULMCIM-C is designed for use with Pull Stations (fast response to alarm)
The ULMCIM-C is identified by the panel as a callpoint.
Code |
ULMCIM and ULMCIM-C |
---|---|
Description |
Single Channel Input Units |
Standards |
UL864 9th edition |
Signalling Line Circuit, Style 7, Class A, Supervised, Power Limited |
|
Current |
332 μA |
Operating Voltage |
24 V dc |
Input, Initiating Circuit Class B, Style C, Supervised, Power Limited |
|
Voltage (8.4 Vpp every 1 second) |
8.4 V dc |
Current |
1.2 mA |
Trigger Resistance |
5.6 k |
End Of Line Resistor |
22 k |
Line Impendance |
16 (max) |
Environmental |
|
Operating Temperature |
0°C to 49°C |
Humidity (Non Condensing) |
0 to 93 %RH |
Physical |
|
Dimensions (H x W x D) |
65mm x 35mm x 18.5mm |
Weight |
>0.1kg |
Ingress Protection |
IP40 |
Compatibility |
|
Suitable for use with |
JSB analogue addressable fire systems |