The ULMCOM and ULMCOM-S are single channel output units and are extremely compact and therefore ideal for incorporation into other equipment.
The ULMCOM is identified by the panel as an input/output unit.
The ULMCOM-S is identified by the panel as a sounder.
The maximum number of ULMCOM-S units per loop is 60, and is counted towards the total number of sounders on the loop.
Code |
ULMCOM and ULMCOM-S |
---|---|
Description |
Single Channel Output Units |
Standards |
UL864 9th edition |
Signalling Line Circuit, Style 7, Class A, Supervised, Power Limited |
|
Current |
0.322 mA (max) |
Output Relay, Supervisory Programmable |
|
Switching Voltage |
24 V dc to 30 V dc |
Contact Rating |
1 A Resistive, pf=1 (max) |
Line Impedance |
16 Ω (max) |
Power Factor |
1 |
Environmental |
|
Operating Temperature |
0°C to 49°C |
Humidity (Non Condensing) |
0 to 93 %RH |
Physical |
|
Dimensions (H x W x D) |
65mm x 35mm x 18.5mm |
Weight |
>0.1kg |
Ingress Protection |
IP40 |
Compatibility |
|
Suitable for use with |
JSB analogue addressable fire systems |