The ULFPTR6000 repeater panel provides sophisticated ‘touch screen’ functionality yet achieves a simple end-user interface operation within a compact panel design.
The ULFPTR6000 is designed to work with all UL Listed Cooper analogue fire alarm control panels as a network repeater. The JSB ‘touch-screen’ repeater panel is easy to install and commission. All text is transmitted via the network and is automatically updated.
Code |
ULFPTR6000 |
---|---|
Description |
Network Repeater Panel, Touch Screen |
Standards |
UL864 9th edition, NFPA 70-72 |
System Indicators |
|
LED’s |
Power on, Alarm, General Trouble, General Supervisory, Power Trouble, System Trouble, Test, NAC Trouble. |
Mains Input, Supervised, Power Limited |
|
Voltage |
120 V ac to 240 V ac, 60 Hz |
Current |
100 mA |
Network SLC |
5 V dv, 11 mA (max) |
Line impedance |
50 ohm (max) |
Batteries |
|
Batteries |
2x12 V dc, 7 Ah, 0.1 derating |
Battery Charge Current |
1.0 Amp |
Standby Period |
24 hours + 30min. alarm |
Programable Relay |
|
Programable Relay (Fire) |
30 V, 1 A, Resistive |
Download Comms |
|
Download Comms |
RS232 port |
Environmental |
|
Operating Temperature |
0°C to 49°C |
Humidity (Non Condensing) |
0 to 93 %RH |
Physical |
|
Dimensions (H x W x D) |
395mm x 332mm x 115mm |
Weight |
9kg (with batteries) 4kg (without batteries) |
Ingress Protection |
IP40 |
Construction |
PC/ABS, UL94 5VA rating |
Colour |
Graphite |
Display |
Touch Screen |
Cable Entry |
11 x 20mm knockouts top of backbox |
Compatibility |
|
Suitable for use with |
JSB UL analogue addressable fire systems |